MBAS 9900 Alarm Annunciator
Introduction: |
It is a Audio Visual Alarm Annunciator. It is best suitable for Control Panels & Switchboards of Diesel Powered Generators, AMF Controllers with trip interlocks, Engine driven Compressors, Fire Fighting Pumps etc. It functions as a complete Annunciator with Control Function to monitor Alarm conditions with both Audio Visual indications. It senses the 12V DC or 24V DC potential contacts & offers output trip contacts for interlocking purpose. It has a built in audible devise. Acknowledged & Reset by built-in push buttons. It consists of 3 basic sections (The Power Pack, The CPU & The Facia) but with an exception that unlike the conventional Annunciators the CPU card accepts 12V DC or 24V DC potential contacts as fault inputs instead of potential free contacts. | |
|
Features: |
· Powerful Microprocessor Circuit. · For 4,6,8 windows (faults) · Fully Integrated Construction. · Built-in System Watchdog LED. · Optically isolated input circuit. · 12V / 24V DC Potential Contact Inputs. · 2 CO Trip Relay Output. · Operates on 24V DC Auxiliary supply. · Built-in Push Buttons (NA for 8 Pt.Model) · Built in Buzzer · Super Bright LED’s · Lower Power Consumption. · AC / DC Auxiliary Supply. · Manual Reset · Auto Reset.
| |
|
| |
|
Application Areas: |
Firstly, where Electrical Control Circuits work on + 24 V dc supply. MBAS 9900 operates on 24V dc supply. Secondly, where the user has to monitor following Alarm conditions with both Audio & Visual indications. Lube. Oil Temperature Lube. Oil Pressure Gen. Over Speed Jacket Water Temperature High Low Fuel Level Spare MBAS 9900 is available in 4 or 6 window configuration which meets the Requirement. Thirdly, where volt free contacts are not available & separate auxiliary relays, control relays are required which adds to the costs. MBAS 9900 accepts + 24V dc contacts directly from the control circuit. Fourthly, external push buttons & audible bell or buzzers are needed for conventional Annunciator. MBAS 9900 comes with built-in Push Buttons & built-in buzzer. Fifthly, where the user needs trip contacts, which is achieved by separate auxiliary relays & interlocked with other control circuits. MBAS 9900 comes with built-in 2CO trip contacts which are interlocked until all fault inputs normalize. Conventional relay & lamp design is always a clumsy design & tedious to trouble shoot. Most would prefer to avoid it as the cost of wiring up the components & labor is not worth it. The aesthetics cannot be better either. Best suitable for Control Panels & Switchboards of Diesel Powered Generators, AMF Controllers with trip interlocks, Engine driven Compressors, Fire Fighting pumps etc. Minilec MBAS 9900 can be used for following applications: The Diesel Generator Sets Panels Auto Mains Failure or Panels Diesel Engine Driven Screw Compressor Panel Diesel Engine Driven Crane Control Panel Gas based Captive Power Generator Panels | |
|
Technical Specifications: |
|
|
|
Specifications |
1 |
Supply Voltage |
230 V AC / 110 V AC, 12 V / 24 V DC / 48 V DC +10% -15% |
2 |
Windows |
4 / 6 |
3 |
Window Sizes |
30 x 30 mm, 30 x 65 mm |
4 |
Display Device |
Super bright high efficiency low power consuming LED's |
5 |
Facia Type |
Individual Windows Front Replaceable |
6 |
Window/LED Colour |
Standard colours available RED, Optional colours Yellow / Amber, Green |
7 |
Flash Rate |
Fast - 60 flashes/min. Slow - 30 flashes/min. |
8 |
Response Time |
25 msec. ± 10 msec. |
9 |
Input Signal |
+12 V or 24 V DC Contact |
10 |
Output Contacts |
1 CO + 1 CO |
11 |
Contact Rating |
5 Amps 240 V AC (Resistive) |
12 |
Architecture |
Integrated |
13 |
Operational Seq. |
Sequence as mentioned in text OR any other sequence on request |
14 |
Operational Temp. |
0 0-60 C |
15 |
Power Consumption |
1.5 Watts per Window | | |
|
|
|