Introduction: |
It is a two level & two tank water level controller. It is best suitable for Automatic Start Stop Control of Pumps for Normal Water with reference to high & low levels in the suction tank & delivery tank. It is also suitable for monitoring single overflow / dry run alarm level in two tanks. It is available for conductive Liquid like water. It is supplied with 6 stainless steel electrodes. Three SS electrodes are immersed in each tank. One acts as a reference level one senses the low level (Restart or Stop) & the high level (Stop or Restart in each tank). The Relay energizes when all three electrodes are inside the liquid in suction tank & all three electrodes are inside the liquid in delivery tank. It de-energizes when delivery tank is full or suction tank is empty. | |
|
Features: |
· Operates by sensing the continuity of electrical signal through the conductive / water medium.
| |
|
| |
|
Application Areas: |
Water Cooled machines Pump Starter panels Water Treatment Plant Transfer Pump Control Booster Pump Control Engine Control Panels Ice Making Machines Air-con equipment & Chillers Steam Generators Boilers Railway Car shed Cooling Water Pump control Pump automation, Safety operation Start-up & Low level Alarm Start-up & High level Alarm Radiator Water Level Alarm Water Storage Level Monitor High Water Level Alarm Low Level Alarm, Heater Safety. Water Tank level Monitor Water Pump Automation Washery | |
|
Technical Specifications: |
|
|
|
Specifications |
1 |
Auxiliary Supply |
24 /110 / 240 / 380 / 415 V AC ±10%, 50 / 60 Hz, 12 / 24 V DC |
2 |
Output Contacts |
1 CO |
3 |
Input Sensors |
6 Electrodes |
4 |
Sensitivity |
N.A. |
5 |
Trip Time Delay |
Less than 1 sec |
6 |
Weight |
Unit 215 gms; Sensor (each) 50 gms |
7 |
Dimensions (mm) |
Unit Overall (L x W x D) 75 x 35 x 95; Mounting (L x W) 11- pin plug-in |
8 |
Sensor |
Overall 24 (Dia) x 76 (L) | |