| Introduction: |
| It is a Negative Sequence Voltage Sensing Phase Failure Relay. It is best suitable for 3 phase loads or 3 phase motor / pump loads only. It offers protection against Phase Failure, Phase Unbalance, Phase Sequence Reversal, Under Voltage & Over Voltage faults. It is useful for incoming side, Mains Supply monitoring, General voltage faults, AMF/Transfer Switch Panels & Pump Control Panels. It is available in DIN Rail mounting enclosure. | |
|
|
| Features: |
· Monitors all 3 Phases of Voltage Supply. · Available for any System Voltage. · External Aux.supply. · Auto Reset. · Sleek DIN Rail mounted Enclosure. · 2 CO output contact.
| |
|
| |
|
|
| Application Areas: |
| Protection for LT, HT Motors Auto Transformer Starter Panels General Purpose machines Motor Starter Panels / MCC s Crane Motor Control Panels Air-conditioning Machines Compressor Control Panels Centrifuge Machines | |
|
|
| Technical Specifications: |
|
|
|
|
|
Specifications |
| 1 |
Supply Voltage |
System 240 / 380 / 415 V AC ±20%; Auxiliary 110 / 240 / 380 / 415 V AC ±20% |
| 2 |
Output Contacts |
2 CO |
| 3 |
Trip Setting (Volts) |
Phase unbalance 30 V to 70 V ±6 V (adjustable); Under Voltage N.A.; Over Voltage N.A.; Water Level N.A. |
| 4 |
Trip Time Delay |
On Phase Failure/Seq. 3.5 sec. ±1.5 sec. |
| 5 |
Resetting Mode |
Auto / Manual / Remote |
| 6 |
Weight |
400 gms. |
| 7 |
Dimensions (mm) |
76 x 56.5 x 117.5; Mounting (L x W) 67 x 46 | | |
|
|
|