| Introduction: |
| It senses the Negative Sequence Voltage components of the system supply. It is best suitable for 3 phase loads or 3-phase motor / pump loads only. It offers protection against Phase Failure, Phase Unbalance, Phase Sequence Reversal. It is useful for monitoring incoming Mains Power Supply for unbalance voltage faults in Air-conditioning & Pump Control Panels. It is available in DIN Rail mounting enclosure. | |
|
|
| Features: |
· Monitors 3 phase Voltage Supply. · Suitable for any System Voltage. · No external auxiliary Supply required (Built in Aux. Supply). · Auto Reset. · 2 CO output contacts. (For 1CO output use VSP D1 model) · Power ON & Trip LED indication. · Sleek DIN Rail mounted D1 Enclosure.
| |
|
| |
|
|
| Application Areas: |
| Hoist motors, small machines, compressor motor. | |
|
|
| Technical Specifications: |
|
|
|
|
|
Specifications |
| 1 |
Supply Voltage |
System 240 / 380 / 415 V AC ±20%; Auxiliary Built-in |
| 2 |
Output Contacts |
2 CO |
| 3 |
Trip Setting (Volts) |
Phase unbalance 40 V ±6 V (fixed); Under Voltage N.A.; Over Voltage N.A.; Water Level N.A. |
| 4 |
Trip Time Delay |
On Phase Failure/Seq. 3.5 sec. ±1.5 sec. |
| 5 |
Resetting Mode |
Auto |
| 6 |
Weight |
320 gms. |
| 7 |
Dimensions (mm) |
Overall (L x W x D) 76 x 30.5 x 117.5 mm; Mounting (L x W) 68 centre to centre | |