MULTI-CHANNEL TYPE CONTROLLER |
Model |
GTC-200A COMMOM (ALARM UNIT) |
GTC-200ACHANNEL (DENSITY INDICATING UNIT) |
Operation display |
8-LEDs (Power, 3-alarm, Trouble Buz. Stop, PC & channel data communication) |
6-LEDs (Power, 3-alarm, Trouble) Stand-by (maintenance)) |
Measuring display |
|
4-Digit FND& Bar-Graph (32 LED) |
Measuring range |
|
1~9999 (programmable) (%LEL, ppm, % Vol) |
Alarm display |
Visual: 3-Alarm, Trouble LEDs Audible: buzzer |
Visual: 3-Alarm, Trouble LEDs |
Alarm output signal |
3-Alarm, Trouble, Buzzer AC250V/5A relay contact (SPST) |
3-Alarm, Trouble AC250V/5A relay contact (SPDT) |
Alarm level set |
|
Programmable within detection range |
Input signal |
|
4-20mA DC (2 wire or 3 wire) |
Output signal |
Isolated RS-485 Modbus (option) |
4-20mA DC |
Reset signal |
Reset switch & remote control |
Reset switch |
Program set mode |
|
Alarm value & type (1, 2, 3 alarm) |
|
|
Alarm time (instant & delay (1~30 min)) |
|
|
Alarm dead band |
|
|
Measuring value compensation (SAD) |
|
|
Relay output on/off |
Operating temperature |
-10∩ ~ +50∩ |
Operating humidity |
0 ~ 99%.RH (non-condensing) |
Operating power |
Single : 18~30V DC (24V DC normal) / 100mA max. |
|
Multi channel type : AC 110 / 220V |
Battery power |
24V DC / 600mA, 1300mA (option) |
|
Aux. power unit (option) |