COMBINE E950-U22 Sieres Voltage Transmitter

Features :
  • Designed and Tested to meet Requirements of IEC 688 and IS 12784
  • Reliable SMD Technology
  • High Insulation Level
  • Higher load Capacity
  • Easy onsite conversion between DIN rail or Panel Mounting
  • Polycarbonate body, conforming to UL 94-VO
     
 
Measuring Quantity
AC Voltage
Nominal Input
110V/110/150/240/ 415/440V
Output Quantity
Independent DC Current or DC Voltage
Output Range
0-1/0-5/0-10 or 0-20mA
4-20mA-2wire connection
0-1OV
Ripple
<1% P-P
Output Burden
Current Output : Rext = 15V / I (full Scale) [750Ω @ 20mA or 1500Ω@ 10mA]
Voltage Output : Rext = Output Voltage/ 20mA,
Auxiliary supply
Self Powered OR 12V - 30V
(only for 2 wire connection with output 4 - 20mA)
Power Consumption
-
Response Time
< 300ms
High Insulation Level
4 kV
Impulse withstand Voltage
5kV, 1.2/50 µsec, 0.5 Ws.
Accuracy as per IEC 688
Class 0.5
Operating Temperature
-25 to 55°C