Method of Detection |
|
Long life electrochemical oxygen sensor
|
|
Ranges Available |
|
0-5.0%, 0-10.0%, 0-25.0%, 0-50.0%
|
|
Resolution |
|
0.1% O2
|
|
Accuracy & Repeatability |
|
±1% of full scale (±2% of full scale above 30% O2)
|
|
Drift |
|
< 2% of full scale for 8 hours of operation
|
|
Response Time (T-90) |
|
8-10 seconds for 90% of step change
|
|
Ambient Temperature Range |
|
0 to 40 ºC 32 to 105 ºF
|
|
Linearity |
|
±1% of full scale
|
|
Size & Weight |
|
10" L x 7 1/2" H x 6 1/2" D @ 8 lbs (25.5 x 19 x 16.5 cm @ 3.6 kg)
|
|
Power |
|
AC/DC Operation, 115 VAC, 60 Hz for recharging (Other voltages available)
|
|
Output Options |
|
0-1 V or 4-20 mA (optional)
|
|
Hazardous Area Rating Options |
|
General Purpose, Non-Hazardous
|
|
| |
|
Analysis of oxygen (O2) in flue gases from any type of fuel. For checking combustion efficiency, air infiltration and burner & control performance of furnaces, heaters and boilers. May be used in commercial, industrial and residential settings.
| |
|
- Rugged design that is easy to operate and maintain
- Fast warm-up and response
- Long life 'fuel cell' oxygen sensor (3-4 year life)
- Digital readout meter with backlight
- Rechargeable battery operation
- Built in sample pump, filter and flow meter
- Continuous condensate removal
- For use on any fuel
- Weatherproof (WP) cabinet with clear Lexan cover
- Stainless steel probe with sample hose
- Pays for itself in months through fuel savings
| |
|
- Outputs of 0-1 V or 4-20 mA
- Special sampling probes
- Sample pre-cooler
- Suitcase (K) style cabinet available
- AC power only operation
- Detachable/portable data logger
| |
|
- On air for span
- On nitrogen for zero
| | |
|
|
|