产品名称:
PFV2多功能相故障继电器
|
PFV2多功能相故障继电器
Introduction: |
It is a Phase Failure with Under & Over Voltage Relay. It is best suitable for protection of balanced 3 phase loads or 3 phase Motor / Pump loads only or for monitoring 3 phase MAINS supply. It offers protection against Phase Failure, Phase Unbalance, Phase Sequence Reversal, Under Voltage & Over Voltage faults. It is useful for incoming side, Mains Supply monitoring, General voltage faults, AMF/Transfer Switch Panels & Pump Control Panels. It is available in 11 pin Plug-in base mounting & flash mounting enclosure. | |
|
Features: |
· Under & Over Voltage (Factory Set). · Monitors Aux.Voltage for Under & Over Voltage. · Monitors all 3 phases of voltage for unbalance & phase loss. · Built-in Aux.Voltage. · Auto Reset. · Panel Flush Mounted Enclosure.
| |
|
| |
|
Application Areas: |
Measures 3-Phase supply for Unbalance Voltage, Loss of Phase, Phase Sequence, Under Voltage & Over Voltage. Best suitable for balance 3 phase loads or motor loads only. Phase failure &UV/OV Relays can be best used for a host of Auxiliary Systems & Plant control panels & machinery. | |
|
Technical Specifications: |
|
|
|
Specifications |
1 |
Supply Voltage |
System240 / 380 / 400 / 415 V AC ± 20%, 50 / 60 Hz; Auxiliary Built-in |
2 |
Output Contacts |
1 CO |
3 |
Trip Setting (Volts) |
Phase unbalance 40 V ± 6 V (fixed); Under Voltage 190 V (fixed); Over Voltage 260 V (fixed); Water Level N.A. |
4 |
Trip Time Delay |
On Phase Failure 3.5 secs ± 1.5 sec.; On UV/OV 10 secs. |
5 |
Resetting Mode |
|
6 |
Weight |
430 gms. |
7 |
Dimensions (mm) |
Overall (L x W x D) 96 x 96 x 76 (flush mounting); Mounting (L x W) 92 x 92 (cutout) | | |
| |
|
|
|