 INFRA RED TYPE COMBUSTIBLE & CO2 GAS DETECTOR  | 
| 
 Model  | 
 | 
  GIR-3000 (CO2)  | 
| 
 Measuring gas   | 
Combustible gas (LNG, LPG, Methane & etc)    | 
 Carbon dioxide (CO2)  | 
| 
 Measuring type  | 
 Diffusion type  | 
| 
 Sensor type  | 
 Infrared type  | 
| 
 Measuring range   | 
0-10,000 ppm & 0-100 % LEL       | 
0-10,000 ppm & 0-5.0% Vol | 
| 
 Sensor life time  | 
 More than 5 years  | 
| 
 Response time  | 
 <10 sec / 90% scale  | 
| 
 Accuracy   | 
 ±3% / Full scale  | 
| 
 Parameter controls  | 
 Non intrusive control with Magnet bar (calibration, maintenance, alarm setting)  | 
| 
 Operation mode display  | 
 4-LED (Power, 2-Alarm, 1-Trouble)  | 
| 
 Measuring value display   | 
 LCD display (Built-in Back light 2-Line, 16 characters)  | 
| 
 Alarm signal output   | 
 250V 1A / 3-SPST Relay contact (2-Alarm, 1-Trouble)  | 
| 
 Output signal   | 
                Analog output : Measuring signal: 4-20 mA DC    | 
| 
     | 
                                             Maintenance signal: 3 mA DC   | 
| 
     | 
                                             Calibration signal: 2 mA DC  | 
| 
     | 
                                             Fault signal: 0 mA DC  | 
| 
     | 
                Digital output :RS-485 MODBUS (Option)   | 
| 
 Cable / Distance   | 
 Power + signal cable: 3 wire (above CVVS 1.5sq) / 2,500m max.  | 
| 
     | 
 RS-485 data communication cable: 1par (UL2919 RS-485) / 1,000m max.  | 
| 
 Conduit pipe   | 
 1/2" & 3/4" PF, NPT (3/4" PF standard)  | 
| 
 Mounting type   | 
 2" Pole mount, Wall mount, Duct mount  | 
| 
 Operating temperature   | 
 -20∩ ~ +50∩  | 
| 
 Operating humidity   | 
 5 ~ 99%.RH (non-condensing)  | 
| 
 Operating power   | 
 18 ~ 31V DC (24V DC normal) / 300mA max.  | 
| 
 Dimensions   | 
 301.5 x 152 x 109 (W X H X D)  | 
| 
 Weight   | 
 2.5kg  | 
| Approval  | 
 Flame proof structure (Ex d IIC T6)  |