产品名称:
362K便携式烟气分析仪
|
|
Method of Detection |
|
Customer replaceable electrochemical O2, CO and NO sensor
|
|
Ranges Available |
|
0-200 to 0-2000 PPM NOx (as NO); 0-1800°F (0-1000°C) net stack temperature (362T) 0-25.0% O2; 0-2000 PPM to 0-4.00% CO (switch selectable)
|
|
Resolution |
|
0.1% O2; 1 PPM on CO and NOx
|
|
Accuracy & Repeatability |
|
<1% of O2; ± 10 PPM CO; ± 3 PPM NOx
|
|
Drift |
|
±2% of full scale per 8 hours of continuous operation
|
|
Response Time (T-90) |
|
10-12 seconds for O2; 20-30 seconds for CO and NOx
|
|
Ambient Temperature Range |
|
0 to 40 ºC 32 to 105 ºF
|
|
Linearity |
|
±1% of full scale of each gas measured
|
|
Size & Weight |
|
10 1/2" W x 14" L x 6" H @ 13 lbs (27 x 35 x 15 cm @ 6 kg)
|
|
Power |
|
AC/DC Operation, 115 VAC 60 Hz for recharging (Other voltages available.)
|
|
Output Options |
|
4-20 mA or 0-1 VDC
|
|
Hazardous Area Rating Options |
|
General Purpose, Non-Hazardous
|
|
| |
|
Analysis of oxygen (O2), carbon monoxide (CO), and oxides of nitrogen (NOx as NO). For checking combustion efficiency, air infiltration, NOx emissions, and burner & control performance of furnaces, heaters, and boilers. May be used in commercial, industrial and residential applications.
| |
|
- Long life electrochemical sensors for each gas
- Rugged design that is easy to operate and maintain
- Fast warm-up and response
- Digital readout meter with backlight
- Rechargeable battery operation
- Built in sample pump, filter, flow meter, and continuous condensate removal
- Weatherproof (WP) cabinet with clear Lexan cover
- Stainless steel probe with sample hose
- For use on any fuel
- Dual CO range: 0-2000 PPM and 0-4.00% CO
- Rapid CO & NOx reading recovery on 'overdose'
- Pays for itself in months through fuel savings
| |
|
- Recorder outputs of 0-1 V or 4-20 mA
- Stack temperature readout (362T)
- Special sampling probes
- Sample pre-cooler
- Suitcase (K) style cabinet available
- AC power only operation
- NOx as NO + NO2
- Detachable/portable data logger
| |
|
- Air for O2 span, CO zero and NOx zero
- Analyzed mixture of CO and NO in nitrogen for CO and NO span and O2 zero
| | |
|
|
|