Method of Detection |
 |
Infrared detector; cannot be burned out due to loss of flow or changing gases
|
 |
Ranges Available |
 |
0-100.0% methane, natural gas or propane
|
 |
Resolution |
 |
0.1% methane, natural gas or propane
|
 |
Accuracy & Repeatability |
 |
±1% of full scale
|
 |
Drift |
 |
±1% of full scale per week
|
 |
Response Time (T-90) |
 |
90% of final reading in 8-10 seconds
|
 |
Ambient Temperature Range |
 |
12-50 ºC 55-120 ºF
|
 |
Linearity |
 |
±2% of full scale
|
 |
Size & Weight |
 |
Approx. 14" L x 6" H x 10 1/2" D @ 8 lbs ( 35.5 x 15.2 x 26.6 cm @ 3.6 kg)
|
 |
Power |
 |
AC/DC Operation. 115 VAC 60 Hz for recharging (220 VAC 50 Hz available)
|
 |
Output Options |
 |
4-20 mA or 0-1 VDC
|
 |
Alarms |
 |
Single audible & visual LED alarm with field-adjustable set point
|
 |
Hazardous Area Rating Options |
 |
General Purpose/Non-hazardous
|
 |