LV D2 多功能相故障繼電器
Introduction: |
It is a Negative Sequence Voltage Sensing Phase Failure Relay with Under & Over Voltage Relay. It is best suitable for protection of balanced 3 phase loads or 3 Phase Motor or Pump Load only or for monitoring 3 Phase MAINS supply. It offers protection against Phase Failure, Phase Unbalance, Phase Sequence Reversal, Under Voltage & Over Voltage faults. It is useful for incoming side, Mains Supply monitoring, General voltage faults, AMF/Transfer Switch Panels & Pump Control Panels. It is available in DIN Rail mounting enclosure. | |
|
Features: |
· Under & Over Voltage (Adjustable). · Monitors Aux.Voltage for Under & Over Voltage. · Monitors all 3 phases Voltage for severe unbalanced & phase loss. · Selectable Aux.Voltage. · Manual or Remote Reset (Link). · Sleek DIN Rail mounted enclosure.
| |
|
| |
|
Application Areas: |
Measures 3-Phase supply for Unbalance Voltage, Loss of Phase, Phase Sequence, Under Voltage & Over Voltage. Best suitable for balance 3 phase loads or motor loads only. Phase failure &UV/OV Relays can be best used for a host of Auxiliary Systems & Plant control panels & machinery. | |
|
Technical Specifications: |
|
|
|
Specifications |
1 |
Supply Voltage |
System 240 / 380 / 415 / 440 V AC ±20%; Auxiliary 110 V (Fixed) |
2 |
Output Contacts |
1 CO (2 CO) |
3 |
Trip Setting (Volts) |
Phase unbalance 40 V ±6 V (fixed); Under Voltage 80% to 95% (adjustable); Over Voltage 105% to 120% (adjustable); Water Level N.A. |
4 |
Trip Time Delay |
On Phase Failure 3.5 secs. ± 1.5 sec; On UV/OV Less than 2 secs. for OV & 2 - 5 secs for UV |
5 |
Resetting Mode |
Manual / Remote |
6 |
Weight |
430 gms. |
7 |
Dimensions (mm) |
Overall (L x W x D) 76 x 56.5 x 117.5; Mounting (L x W) 67 x 46 | |
|
|
|
|