PFS2 相故障繼電器
Introduction: |
It is a Phase Failure Relay. It is best suitable for protection of balanced 3 phase loads or 3 phase Motor / Pump loads only. It offers protection against Phase Failure, Phase Unbalance, Phase Sequence Reversal, Under Voltage & Over Voltage faults. It is useful for incoming side, Mains Supply monitoring, General voltage faults, AMF/Transfer Switch Panels & Pump Control Panels. It is available in 8 pin Plug-in base mounting & flash mounting enclosure. | |
|
Features: |
· Monitors all 3 phases of Voltage Supply. · Built-in Auxillary Supply. · LED Indications for Power ON & Fault. · Auto Reset. · 8 PIN socket base mounted Enclosure.
| |
|
| |
|
Application Areas: |
It is useful for monitoring incoming Mains Power Supply for unbalance voltage faults in Air-conditioning & Pump Control Panels. It is available in DIN Rail mounting enclosure. | |
|
Technical Specifications: |
|
|
|
Specifications |
1 |
Supply Voltage |
System 110 / 240 / 380 / 415 V AC ±10%, 50 / 60 Hz; Auxiliary Built-in |
2 |
Output Contacts |
1 CO |
3 |
Trip Setting (Volts) |
Phase unbalance 40V ± 6V (fixed); Under Voltage N.A.; Over Voltage N.A.; Water Level N.A. |
4 |
Trip Time Delay |
On Phase Failure/Seq. 3.5 sec. ±1.5 sec. |
5 |
Resetting Mode |
Auto |
6 |
Weight |
175 gms. |
7 |
Dimensions (mm) |
Overall (L x W x D) 50 x40 x 80; Mounting (L x W) 8 - Pin Plug-in | |
|
|
|
|