語言:       
高 品 質 產 品

專 業 化 服 務
 
  公司簡介
  產品目錄
  新聞中心
  支持與服務
  解決方案與應用
  銷售網絡
  聯繫我們




PS D1相故障繼電器

Introduction:
It is a compact version of SP D2. It senses the Negative Sequence Voltage components of the system supply & offers protection against Phase Failure, Phase Unbalance, Phase Sequence Reversal. The user can set the unbalance voltage as per field requirements & optimally use the motors. It is useful for monitoring incoming Mains Power Supply for unbalance voltage faults in Motor Control Panels. It is available in DIN Rail mounting enclosure.
Features:
· Monitors 3 Phase Voltage Supply.
· Suitable for any System Voltage
· Manual / Remote /Auto Reset (Selectable)
· Fault Trip Indications (LED’s)
· 2 CO output contacts 2 CO output contacts
· Sleek DIN Rail mounted D1 Enclosure.
Application Areas:
It is useful for monitoring incoming Mains Power Supply for unbalance voltage faults in Motor Control Panels. It is available in DIN Rail mounting enclosure.
Technical Specifications:
Sr.
Parameter
Specifications
1 Supply Voltage System 240 / 380 / 415 V AC ±20%; Auxiliary 110 / 240 / 380 / 415 V AC ±20%
2 Output Contacts 1 CO
3 Trip Setting (Volts) Phase unbalance 30 to 70 V ±6 V (adjustable); Under Voltage N.A.; Over Voltage N.A.; Water Level N.A.
4 Trip Time Delay On Phase Failure/Seq. 3.5 sec. ±1.5 sec.
5 Resetting Mode Auto
6 Weight 320 gms.
7 Dimensions (mm) Overall (L x W x D) 78 x 30.5 x 117.5; Mounting (L x W) 68 centre to centre

相關下載
 
2000©Copyright 2000 康寶萊儀表(珠海)有限公司 allrights revered
地址:中國廣東省珠海市(國家)高新技術産業開發區金峰西路40號
電話:+0086 756 3895799 傳真:0086 756 3892788 郵箱:sales@combine-inst.com  网站备案/许可证号:粤ICP备16107310号